News

Henan Zhongyue Valve Manufacturing Co. Ltd
— 采暖管道堵塞原因分析預防措施 —

采暖管道堵塞原因分析預防措施


現象:
采暖系統投入使用后,管道堵塞或局部堵塞,影響蒸氣或熱水流量的合理分配,使采暖系統不能正常工作,甚至使管道或爐片凍裂,嚴重影響使用。
原因分析:
(1)管道安裝時,管口封堵不及時或封堵不嚴,有雜物進入堵塞管道;
(2)管道安裝時,用氣割割口,熔渣落入未及時取出而堵塞管道;
(3)管道進行焊接時,對口間隙過大,焊渣流入,集到一起堵塞管道;
(4)管道加熱彎管時,殘留在管內的砂子未清理干凈;
(5)鑄鐵爐片內砂子未清理干凈,通水后流入管道;
(6)管道安裝完畢,系統沒有按規定要求進行吹洗,大量污物沒有排出;
(7)閥門的閥芯自閥桿上脫落,堵塞管道。
預防措施:
(1)進行管道安裝時,應隨時將管口封堵,特別是立管,更應堵嚴,以防交叉施工,異物落入;
(2)盡量不采取氣焊割口,如必須使用時,必須及時將割下的熔渣清出管道;
(3)無論采用電焊或氣焊,均應保持合格的對口間隙;
(4)管道采用灌砂加熱彎管時,彎管后必須徹底清除管內砂子;